Each model is checked against the references the field uses to check its own simulators, with the reference's tolerance, and the results are these.
The method is the same for every model. We take a published reference for that physics, run its cases through our own code, and import its results as tests with the tolerance its authors use, before adding any case of ours. The references are named because they are the check; nothing here is endorsed by anyone, it is reproduced. For the coolant loop the reference is the Modelica Buildings Library, version 14, from Lawrence Berkeley National Laboratory, an open, peer-reviewed library of liquid-cooled data center components whose authors publish the results of their own example runs; its regression gate is 0.1 % of the value or 0.001 in absolute terms, whichever is larger, about 0.3 K on a temperature and 0.001 on a valve position.
| Case | What is compared | Tolerance | Result |
| Coolant loop · Lawrence Berkeley National Laboratory's Modelica Buildings library, version 14 · 469 tests |
| The library's own coolant distribution unit example: one unit, one rack, 2 hours, with a step in the rack's heat | All 14 time-varying signals: supply and return temperatures, case temperature, valve position, pump power and pressure, exchanger duty, rack pressure drop, at a 0.1 s step | 0.1 % or 0.001, as the library uses | All 14 within tolerance at every point; energy integrals within 0.002 % |
| A demo hall of 8 racks on one unit, 7 scenarios: baseline, facility water 3 K warmer, a unit trip, a rack isolated, and others | Every rack's inlet and outlet temperature, flows, pump speed, unit pressure drop and return temperature, at a 1 s step | 0.1 % or 0.001, with a 2 s time allowance where an input steps | Flows, pump speed, pressure drop and return temperatures within tolerance in all 7; the worst temperature difference is 0.13 K on rack outlets after the unit trip |
| A multi-unit reference hall with row headers and per-rack valves, built from the library's own components, the same 7 scenarios | Rack-level and unit-level signals through the trips and the warm-water case | As above | No rack-level signal outside tolerance; facility return through a unit trip within 0.16 K; the largest difference, 0.71 K, is on a unit's return during the start-up front of the baseline, where sharp temperature fronts differ between any two good simulators and are reported rather than gated |
| Power distribution, load flow · the IEEE 13-node distribution test feeder · 291 tests across the power model |
| The IEEE 13-node test feeder, the case the power-systems community publishes to check load-flow solvers | Input, load and losses per phase; 15 node voltages; 11 segment currents and their losses | 0.1 % on power; 0.0003 per unit on voltage; 0.05 % on current | Input power within 0.001 %; voltages within 0.00023 per unit; currents within 0.02 % |
| Power distribution, short circuit · IEEE 13-node short-circuit test case and IEC 60909-4 |
| The IEEE 13-node short-circuit test case, and the worked meshed example of IEC TR 60909-4 | Three-phase and line-to-ground fault currents at 9 buses; initial short-circuit current at 5 buses | 0.1 %; 1 A | Within 0.01 %; within 0.1 A |
| Device limits · IEC 60076-7 worked example and CIGRE TB 880 references |
| The worked example of IEC 60076-7 for transformer hot spot and ageing; the free reference cases of CIGRE Technical Brochure 880 for the IEC 60287 cable ratings | Hot-spot temperature at 6 checkpoints through an overload cycle; cable current ratings case by case | 1.5 K on the hot spot; the brochure's own figures on the ratings | Worst 1.05 K, the same figure an independent transcription of the standard's example reaches; ratings within the brochure's figures |
The continuous limits themselves rest on IEEE C57.91 and IEC 60076-7 for transformers, IEEE C57.110 for harmonic derating, IEC 60287 and IEC 60853 for cables, IEC 60947-2 and UL 489 for breakers, UL 1008 for transfer switches, IEC 61439 for assemblies and NEC 310 for conductors, each cited at the rule where it is used.
Verification and validation are two different checks. Verification is what the table shows: our code reproduces a published reference within its tolerance, once, before the model is used anywhere. Validation is per hall: the model is calibrated on that hall's own readings in the first weeks of an engagement, and the calibration report states how close each device's model is to what the hall measures before any limit is credited on it.
What the reference hall demonstrates is the coupled hydraulics and thermal behaviour of a hall through unit trips, rack isolation and warmer facility water: who gets the flow when a unit is lost, how the headers share it, how fast each rack's inlet and case temperature move. What it does not settle is any real hall's own numbers: the pump curve of its units, the flow resistance of each rack against its catalogue value, exchanger fouling and sensor lags. Those are what validation measures. The reference runs are kept as files, with the scripts that produced them.